XM31-915-HP - 10298645
Power Supply
Alarms
Battery
Log In...
English
Español
Français
Português
Deutsch
Overview
Hardware
Power Supply
Batteries
Environmental I/O
Components
Network
Ethernet
Advanced
Interfaces
Network Services
Management
System Data
SNMP
Alarms
Utility Power
History
Power Supply Events
Power Supply Configuration
Battery Events
Standby Events
Alarm Log
d
Power Supply
Model
ALPHA/XM31-915-HP
Firmware
V2.06.0
Major Alarm
OK
Minor Alarm
String A balancing: check battery 3
Operational Mode
Line
Charger Mode
Float
Tamper
Door closed
Power Supply Language
English
Power Supply Priority
Normal
d
Input
AC Line Mode
OK
Voltage
121.53
V
Current
6.00
A
Power
625
W
Frequency
60
Hz
Tap Status
Normal
Frequency Range
3.00
Hz
Current Limit
17.00
A
Input Power Consumption
1,517
Wh
1
Output
Voltage
86.77
V
Power
496
W
Apparent Power
574.41
VA
Frequency
59.96
Hz
Percent Load
44.20
%
Output Setting
90 V
Output Regulation
Coarse override
Over-current Tolerance
3.000
sec
Retry Delay
60
sec
Retry Limit
20
Active Drop Alarm
OK
Active Drop Threshold
50
W
Current
6.62
A
d
Inverter
Inverter Status
Off
End of Discharge Type
String
End of Discharge Level
1.75
V/cell
Reduced Peak Mode
Enable
Total Standby Events
49
Time Since Last Standby Event
18d 1h:49m
Time in Last Standby Event
0d 0h:01m
Total Time in Standby
439
min
Standby Events Since Reset
19
Time in Standby Since Reset
98
min
Time Since Reset
511
day(s)
Total Run Time
511
day(s)
Transformer Run Time
511
day(s)
Total Downtime
0d 0h:00m
Oil Cap Lifespan Consumed
13.9
%
d
Self Test
Deep Discharge Cycle
Timed
Test Countdown
2
day(s)
Test Duration
10
min
Test Interval
30
day(s)
Test Inhibit
No
→ CSV
→ Excel
Copyright © 2017-2023 EnerSys. All Rights Reserved.